Overview
-
CE approved – Single Loop Analogue addressable fire alarm panel with 127 devices of any combination with 20 loop powered sounders in addition .supports single repeater panel,Touch key panel with USB inbuilt for Laptop connectivity. Front Panel programmable.
-
- Switched mode power supply
- Modular Construction, Serviceability
- Surge Protection.
- Battery polarity and deep discharge protection.
- Unique protocol feature for fast alarm response.
- Touch Keypad for user friendly operation.
- Auto learning facility
-
Electrical Specification
Primary Power
120 / 220VAC + 10% -15%, 60 / 50 HzStandby Power
12V DC(1 No. of 12V,4.5Ah Sealed Lead acid battery)Operating Condition
Operating Temperature : 0-49° C/32-120° F.
Relative Humidity : 93 ± 2% RH (non-condensing) at 32 ±2° C/ 90 ±3° F.Signaling Line Circuits
Class A or Class B wiring.
No Devices : Max. 127 devices exclusive of loop sounder
Loop resistance : 40Ω (Max.).
Loop capacitance : 0.6 µf (Max.).
Loop Current : 300mA (Max.).Notification Appliance Circuits
Class B, Style – Y wiring
Operating Nominal Voltage : 24 VDC
Current for NAC : 1.0A
Line Drop : 2.4V
End-Of-Line Resistor : 4K7, ½ wattD.C. Output
24VDC regulated, 300mA Max.
Type : Form C
No of Relays : 1
Relay Contact Rating : 2A @ 30 VDC,0.5A @ 125VACCompatible Devices
MODEL DESCRIPTION RE-337-SHL Photoelectric & Heat detector RE-337-SL Photoelectric smoke detector RE-337-HL Heat detector RE-737MC Control Module RE-737MM Monitor Module RE-737MR Relay Module RE-737MZ ZoneModule RE-737MX Input Output Module RE-374BS Sounder base RE-374BI Isolator Base RE-737M Manual call point RE-24ES Loop powered sounder Ordering Information
MODEL Loop MonitI Single loop analogue addressable fire alarm panel