RE-104-4 Zones
Overview
-
The microprocessor based 4 Zone CE mark conventional fire alarm control panel is a standalone system, with 16 X 2 LCDcharacter, 4 zones detection circuit,3 common potential free contacts & a common NAC sounder output, wall/ceiling mounted, Switch mode power supply- SMPS & Battery polarity & Deep discharge protection.
-
RE-104 fire alarm control panel is designed with unique protocol to be used for small commercial building and small scale industries. The system is user friendly with includes all standard to ensure ease for use and high reliability.
-
- Ravel Indian Manufacturer, International standard.
- Switch Mode Power Supply.
- Modular Construction, Serviceable.
- Surface Mount Technology.
- Battery polarity & deep discharge protection.
- As per IS -15908: 2011 Standard.
- 16 X 2 Dot Matrix LCD Display.
- Standby battery backup with built in charging.
- Fire / Fault status in unambiguous colored LED indication.
- Switch Mode Power Supply.
- Tactile Keypad for easy panel operation.
- System on indication.
- Main, Standby status indication.
- Low Battery visual warning with audible tone.
- Relay output for actuators for Fire and Fault.
- Lamp Test facility
- Zone wise one man walk Test Facility.
- Zone wise Isolation facility with loop voltage cut off.
- Compatible to all type of Conventional Detectors.
- Optional Zone Wise Sounder / Zone Wise Contact.
-
Electrical Specification
Primary Power
120 – 220VAC , 50 HzCommon Relays
Type : Form C
No of Relays : 3
Relay Contact Rating : 2Amps @ 30 VDC, 0.5Amps @125VAC.
Power Factor : 1Standby Power
24V D.C (2 Nos of 12v, 7Ah Sealed Lead acid battery).
Quiescent current : 55mAOperating Condition
Operating Temperature : 0 – 49° C/32-120° F.
Relative Humidity : 93 ± 2% RH (non- condensing) at 32 ±2° C/90 ±3° F.Initiating Device Circuits (Zone Circuit)
All zones are Class B wiring
Normal Operating Voltage : 14- 21 VDC
Alarm Current : 15 – 30mA
Short Circuit Current : 42mA Maximum
Loop resistance : 50 ohms Maximum
End-Of-Line Resistor : 4.7K, 1/4watt
Standby Current : 6.8mA (2.4mA for Detectors)Charging Circuit
Charging Voltage 28.2V, ±0.5V
Charging Current 0.5 A (Max.).Notification Appliance Circuits
Class B wiring
Operating Nominal Voltage : 24VDC
Current for NACs : 0.6 Amp
End-Of-Line Resistor : 4K7, 1/4 wattMechanical Specification
Dimensions : (350W X 250H X 100D) Color : Red / White Construction : 18 Gauge (1.22mm) CRCA sheet with powder-coated Finish IP Rating : IP50 Cable Entry : 11xø19mm Knockout in top of the cabinet Ordering Information
Model Description RE-104-R 4 ZONE Fire Alarm Panel RE-104-W 4 ZONE Fire Alarm Panel Note:
R- Red Color, W-White ColorCompatible Devices
Model Description RE-316S-2L Photoelectric Smoke detector with base. RE-316H-2L Heat detector with base. RE-316SH-2L Photoelectric & Heat detector with base